Search

AH2E112S ASCO 120V ACUATOR 6/14SEC PRFOFCLSR

Manufacturer: Asco
Specifications - Power Requirement: 220 VA max. - Closing Time: One second max. Opening Time: - Fast Opening: 14 seconds max. - Slow Opening: 26 seconds max. *Note: Opening time is double between -30˚F and -40˚F ambient. Opening time increases 20% when operating on 50Hz*. Volts/Hz - 120/60 - 110/50 Amps Run - 2.1 @ 120/60 - 2.5 @ 110/50 Amps Hold - 0.09 @ 120/60 - 0.10 @ 110/50 Duty Cycle Continuous - (CPH @ 150F) Ambient Temp -40 to 150 F (-40C to 66C) Installation AH2E Hydramotor mounts in any position directly to a V710 valve with 3 set screws. Electrical - Standard voltages: 120V/60Hz, 110V/50Hz - Non-standard voltages: 24V/60Hz, 240V/60Hz, 220V/50Hz Proof of Closure Switch: (optional) A factory set, non-field adjustable SPDT switch. 1800VA max. connected load (e.g. one 15A max. load @ 24V or 120V; one 7.5A max. load at 240V). Auxiliary Switches: (optional) One or two integral SPDT switches; field adjustable to actuate at any position of stroke. 1800 VA max. connected load (e.g. one 15A max. load @ 24V or 120V; one 7.5A max. load at 240V). (Only one aux. switch available with proof of closure construction.) Damper Arm Rating - Drives damper in one direction only. 20 lb. max. at 2.85” radius at 20˚F to 150˚F and 10 lb. max. at -40˚F to 20˚F. Travel 2" max. The AH2E Hydramotors are push-type, self-contained, electrohydraulic linear actuators which extend when powered and retract by spring force upon power interruption. AH2E Hydramotors provide a fast spring return shutoff time of one second or less. When the actuator is mounted to a V710 gas valve, position indicators on both sides of the actuator show the open or closed position of the valve. The AH2E Hydramotor/V710 gas valve combination provides main line gas control for a wide range of applications, including boilers, furnaces, ovens and all types of industrial and commercial burners. It is available in either a slow or fast opening construction Approvals: UL listed to standard 429 "Electrically Operated Valves," Guide YIOZ, File MP932 Safety Valves FM Approved to Class 7400 “liquid and gas safety shutoff valves." CSA Certified to: - Automatic Gas Valves ANSI Z21.21 CSA 6.5, C/I, File 109157 and 113070. - Automatic Gas Safety Shutoff Valves (CGA 3.9), File 113070 AH2E112S
SKU: ASCO:AH2E112S
Product Availability: 1
$2,999.99
This product must be purchased in increments of 1
i h

Specifications
- Power Requirement: 220 VA max.
- Closing Time: One second max.

Opening Time:
- Fast Opening: 14 seconds max.
- Slow Opening: 26 seconds max.
*Note: Opening time is double between -30˚F and -40˚F ambient.
Opening time increases 20% when operating on 50Hz*.

Volts/Hz
- 120/60
- 110/50

Amps Run
- 2.1 @ 120/60
- 2.5 @ 110/50

Amps Hold
- 0.09 @ 120/60
- 0.10 @ 110/50

Duty Cycle Continuous
- (CPH @ 150F)

Ambient Temp -40 to 150 F (-40C to 66C)

Installation
AH2E Hydramotor mounts in any position directly to a V710 valve with 3 set screws.

Electrical
- Standard voltages: 120V/60Hz, 110V/50Hz
- Non-standard voltages: 24V/60Hz, 240V/60Hz, 220V/50Hz

Proof of Closure Switch: (optional)
A factory set, non-field adjustable SPDT switch. 1800VA max. connected load (e.g. one 15A max. load @ 24V or 120V; one 7.5A max. load at 240V).

Auxiliary Switches: (optional)
One or two integral SPDT switches; field adjustable to actuate at any
position of stroke. 1800 VA max. connected load (e.g. one 15A max. load
@ 24V or 120V; one 7.5A max. load at 240V).
(Only one aux. switch available with proof of closure construction.)

Damper Arm Rating
- Drives damper in one direction only. 20 lb. max. at 2.85” radius at 20˚F to 150˚F and 10 lb. max. at -40˚F to 20˚F. Travel 2" max.

The AH2E Hydramotors are push-type, self-contained, electrohydraulic linear actuators which extend when powered and retract by spring force upon power interruption.

AH2E Hydramotors provide a fast spring return shutoff time of one second or less. When the actuator is mounted to a V710 gas valve, position indicators on both sides of the actuator show the open or closed position of the valve.

The AH2E Hydramotor/V710 gas valve combination provides main line gas control for a wide range of applications, including boilers, furnaces, ovens and all types of industrial and commercial burners. It is available in either a slow or fast opening construction

Approvals:
UL listed to standard 429 "Electrically Operated Valves," Guide YIOZ, File MP932 Safety Valves FM Approved to Class 7400 “liquid and gas safety shutoff valves." CSA Certified to:
- Automatic Gas Valves ANSI Z21.21 CSA 6.5, C/I, File 109157 and 113070.
- Automatic Gas Safety Shutoff Valves (CGA 3.9), File 113070

AH2E112S

Products specifications
Manufacturer Asco