The 0014-IFC with an Integral Flow Check is designed to reduce installation costs when zoning with “00” circulators on medium head/medium flow hydronic or radiant heating, hydro-air fan coils or closed loop solar heating systems. By locating the patented IFC inside the pump casing, a separate in-line flow check is eliminated, reducing installation costs. The reduced pressure drop of the IFC increases the flow performance over in-line check valves. Both the IFC and cartridge are easily accessed for service instead of replacing the entire unit. Available in Cast Iron construction.
Features
• Integral Flow Check (IFC) Patent # 5,664,939
Prevents gravity flow
Eliminates separate in-line flow check
Reduces installed cost, easy to service
Improved performance vs. In-line flow checks
• Unique replaceable cartridge-Field serviceable
• Unmatched reliability-Maintenance free
• Quiet, efficient operation
• Direct drive-Low power consumption
• Self lubricating, No mechanical seal
• Standard high capacity output-Compact design
• Wide range of applications
• Cast Iron construction, Flanged connections
Materials of Construction
Casing (Volute): Cast Iron
Integral Flow Check
Body, Plunger.....Acetal
O-ring Seals.......Nitrile
Spring..............Stainless Steel
Stator Housing: Aluminum
Cartridge: Stainless Steel
Impeller: Non-Metallic
Shaft: Ceramic
Bearings: Carbon
O-Ring & Gaskets: EPDM
Performance Data
Flow Range: 0 - 24 GPM
Head Range: 0 - 22 Feet
Minimum Fluid Temperature: 40°F (4°C)
Maximum Fluid Temperature: 230°F (110°C)
Maximum Working Pressure: 125 psi
Connection Sizes: 3/4”, 1”, 1-1/4” or 1-1/2” Flanged
Electrical Data
Volts: 115
Hz: 60
Ph: 1
Amps: 1.55
RPM: 3250
HP: 1/80014-F1-IFC, 0014-1IFC