REPLACES:
■ Reznor: 257010
FEATURES:
√ With lockout delay and damper control input
√ Intermittent pilot gas ignition control module
√ For use with intermittent pilot boilers, furnaces and other heating appliances
√ Microprocessor-based
√ Monitors timing, Trial for ignition, flame sensing and lockout
√ Remote flame sensing
√ 2 minute Trial for ignition
√ 60 minute lock out if pilot flame is not sensed in 2 minutes
√ Compatible with LP or natural gas
√ Damper control input
SPECIFICATIONS:
■ Control voltage: 18-30 VAC
■ Frequency: 50/60 Hz
■ Pilot valve: 2A @ 24 VAC
■ Main gas valve: 2A @ 24 VAC
■ Current draw: 100 mA maximum
■ Pre-purge delay: 0 seconds
■ Operating temperature: -40°F to 165°F, -40°C to 75°C
■ Humidity: 5%-95% R.H. (non-condensing) at +55°C
■ Trial for ignition: 2 minutes
■ Lock out time: 60 minutes