1 INCH SINGLE STAGE GAS VALVE.4.OWC 120V

Manufacturer: Honeywell
V4943N1012 HONEYWELL 1 INCH SINGLE STAGE GAS VALVE.4.OWC 120V - 120V - 60Hz - 0.055 Amps - 1/2 PSI Max - Factory Pressure Setting 3.5" W.C. - Power Consumption Max 6.6 VA - Pressure Regulation Single Stage - Type of Gas Natural Gas - Has 2 Lead wires - Temp Range - 40 to 150 F - Max Capacity ( CFH) 1000 CFH - CFH Range 300 to 1000 - Lead Wire Length 30 " - 1/4" Spade Terminal - 1" Inlet Size Features - Models are available for natural or liquid petroleum (LP) gases. - Valve models L, N are rapid opening (less than six seconds) and fast closing, and are available for LP and natural gases, respectively. - Line voltage with two-wire thermostat or controller is used with V4943; V8943 is used with 24V thermostat or controller. - V4944 is used with line voltage dual-stage thermostat or controller; V8944 is used with 24V dual-stage thermostat or controller. - Slow opening B,C valve models are available for natural and LP gases respectively. - Valve closes on power failure; recommended for final shutoff service. - Valve closing time: 2 seconds maximum at 7 inches wc inlet pressure. - Valves rated for 0.5 pound per square inch (psi) (3.4 kPa) - Lead wires and cover for electrical conduit connections are provided. The V4943/V8943B and N (single stage) and V4944/V8944B and N (two stage) are solenoid-operated diaphragm valves suitable for natural gas only. The V4943/V8943C and V4944/V8944C and L are solenoid-operated diaphragm valves suitable for Liquefied Petroleum (LP) gas only. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters.
SKU: HONEYWELL:V4943N1012
Product Availability: 1
$380.41
This product must be purchased in increments of 1
i h

V4943N1012 HONEYWELL 1 INCH SINGLE STAGE GAS VALVE.4.OWC 120V

- 120V
- 60Hz
- 0.055 Amps
- 1/2 PSI Max
- Factory Pressure Setting 3.5" W.C.
- Power Consumption Max 6.6 VA
- Pressure Regulation Single Stage
- Type of Gas Natural Gas
- Has 2 Lead wires
- Temp Range - 40 to 150 F
- Max Capacity ( CFH) 1000 CFH
- CFH Range 300 to 1000
- Lead Wire Length 30 "
- 1/4" Spade Terminal
- 1" Inlet Size

Features
- Models are available for natural or liquid petroleum (LP) gases.
- Valve models L, N are rapid opening (less than six seconds) and fast closing, and are available for LP and natural gases, respectively.
- Line voltage with two-wire thermostat or controller is used with V4943; V8943 is used with 24V thermostat or controller.
- V4944 is used with line voltage dual-stage thermostat or controller; V8944 is used with 24V dual-stage thermostat or controller.
- Slow opening B,C valve models are available for natural and LP gases respectively.
- Valve closes on power failure; recommended for final shutoff service.
- Valve closing time: 2 seconds maximum at 7 inches wc inlet pressure.
- Valves rated for 0.5 pound per square inch (psi) (3.4 kPa)
- Lead wires and cover for electrical conduit connections are provided.

The V4943/V8943B and N (single stage) and V4944/V8944B and N (two stage) are solenoid-operated diaphragm valves suitable for natural gas only. The V4943/V8943C and V4944/V8944C and L are solenoid-operated diaphragm valves suitable for Liquefied Petroleum (LP) gas only. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters.

Products specifications
Manufacturer Honeywell