C7400A2001 ENTHALPY SENSOR DUCT 4/20MA OUTPUT REPLACES C7400A1004

Manufacturer: Honeywell
Output Signal: 4 to 20 mA current signal increases from 4 mA to 20 mA as enthalpy decreases. Operating Ambient Temperature Range: -25°F to +125°F Shipping Temperature Range: -40°F to +150°F Maximum Power Consumption: 0.45 VA. Supply Voltage: 18-24 Vdc. Electrical Connections: Two 1/4 in. (6 mm) quick connect terminals. Features • Senses and combines temperature and humidity of outdoor air. • Long lasting solid state thermistor sensing element is accurate and stable over time. • As enthalpy of outdoor air increases, the outdoor air damper closes to a preset minimum position. • As enthalpy of outdoor air becomes low, the outdoor air damper opens to reduce the cooling load in the building. • Maximum economizer savings is achieved when two C7400A Solid State Enthalpy Sensors are connected to one W7459 Solid State Economizer Control for differential enthalpy changeover control. • Compact size and lightweight construction. Allows easy mounting in HVAC rooftop unit. • Sensor is enclosed in a rugged, corrosion-resistant glass-fiber reinforced plastic duct-mount case. • Provides a 4 to 20 mA output signal to W7459 Solid State Economizer Control; setpoint is located on solid state economizer control. Used With: - W7210 Economizers - W7212A Economizers - W7213 Economizers - W7214 Economizers - W7215 Economizers - W7459 Economizers - W7460 Economizers The C7400A Solid State Enthalpy Sensor is used with the W7459 Solid State Economizer Control Package. It permits the use of outdoor air as the first stage of cooling in heating, ventilating and air conditioning (HVAC) systems.
SKU: HONEYWELL:C7400A2001
Product Availability: Out of stock
$113.69
This product must be purchased in increments of 1
i h

Output Signal: 4 to 20 mA current signal increases from 4 mA to 20 mA as
enthalpy decreases.
Operating Ambient Temperature Range: -25°F to +125°F
Shipping Temperature Range: -40°F to +150°F
Maximum Power Consumption: 0.45 VA.
Supply Voltage: 18-24 Vdc.
Electrical Connections: Two 1/4 in. (6 mm) quick connect terminals.

Features
• Senses and combines temperature and humidity of outdoor air.
• Long lasting solid state thermistor sensing element is accurate and stable over time.
• As enthalpy of outdoor air increases, the outdoor air damper closes to a preset minimum position.
• As enthalpy of outdoor air becomes low, the outdoor air damper opens to reduce the cooling load in the building.
• Maximum economizer savings is achieved when two C7400A Solid State Enthalpy Sensors are connected to one W7459 Solid State Economizer Control for differential enthalpy changeover control.
• Compact size and lightweight construction. Allows easy mounting in HVAC rooftop unit.
• Sensor is enclosed in a rugged, corrosion-resistant glass-fiber reinforced plastic duct-mount case.
• Provides a 4 to 20 mA output signal to W7459 Solid State Economizer Control; setpoint is located on solid state economizer control.

Used With:
- W7210 Economizers
- W7212A Economizers
- W7213 Economizers
- W7214 Economizers
- W7215 Economizers
- W7459 Economizers
- W7460 Economizers

The C7400A Solid State Enthalpy Sensor is used with the W7459 Solid State Economizer Control Package. It permits the use of outdoor air as the first stage of cooling in heating, ventilating and air conditioning (HVAC) systems.

Products specifications
Manufacturer Honeywell