Satronic IRD1010.1 Art. Nr. 1657105 Flame monitoring device for yellow- or blueburning oil flames Heatwise Part Number 1657105 INTRODUCTION The IRD 1010.1 is employed to monitor the flame of an oil burner. This flame monitoring device should be connected to a Satronic oil burner control box. Monitoring is based on the infra-red flicker principle, in other words, the flickering infra-red light of the flame is detected. The steady radiation from, for example, the glowing refractory layer on the inside of the boiler, has no effect on the detector. The IRD 1010.1 replaces the IRD 1010, 910, 911 and 911vi. When exchanging the IRD 1010, care must be taken that the corresponding IRD 1010.1 with the same imprint (blue, white or red) is used. When exchanging the IRD 910, 911 or 911vi, care must be taken to wire the sensor correctly. For replacement of the IRD 910, 911 or 911vi with IRD 1010.1 is the 50000094-001 sensor cable also needed. The infra-red flicker detector is suitable for use with the following control boxes: IRD 1010.1 DKO 970, 972, 974, 976, 992, 996 DKW 974, 976 DMO 976 TF 801, 802, 804 TF 830, 832, 834, 836 TF 844, 874, 876, 974, 976 MMD 900, 900.1, TTO 872, 876 MMO 872, 876 TMO 720-4 CONSTRUCTIONAL FEATURES The infra-red sensor and the pre-amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector. Wiring is by way of a plug connection. The sensitivity control and two LED’s for indication of the flame signal are situated on the rear of the flicker detector. TECHNICAL DATA Supply voltage 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz) Nominal current input approx. 4 mA Power consumption 1 VA Ambient temperature -20° C to +60° C Insulation standard IP 41 Mounting attitude any Weight 40 g Flame viewing attitude side-on or end-on according to type Spectral response 800 - 1100 nm (with daylight filter) maximum 950 nm Frequency range 15 Hz.... 250 Hz (-12 dB) Sensitivity adjustment range approx. 1 : 20 (26 dB) Switch-on delay < 3.5 sec. (after connecting operating voltage) Response time < 0.1 sec. Cut-out time < 1 sec. Approved ambient parameter max. 95% at 30° C - for operation -20° C... +60° C - for storage -20° C... +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 230, as well as all other relevant Directives and standards