BARBER COLEMAN DIRECT ACTING TWO PIPE THERMOSTAT 55 TO 85F W
BARBER COLEMAN DIRECT ACTING TWO PIPE THERMOSTAT 55 TO 85F W
The Barber Colman (Schneider Electric) 2212-118 Direct Acting, Two-Pipe Thermostat, 55 to 85F, w/o Dial Limit Stops, Kit includes hardware/fittings, metal base, tube, cover, and instructions (2212-118-1).
The 2212-118 and 2212-119 Series Pneumatic Room Thermostats are designed for proportional control of pneumatic devices and actuators in environmental control systems. These two-pipe thermostats incorporate a highly sensitive bimetal thermostatic element and a pilot operated relay with pneumatic feedback for accuracy and stability over the entire operating range.
These thermostats have a serrated thumb wheel for setpoint adjustment
Specifications
Action: Proportional.
Setpoint Range: 55 to 85 °F (13 to 29 °C).
Throttling Range: 2 to 12 °F, adjustable.
Supply Air Pressure: 20 psig.
Maximum Air Pressure: 30 psig.
Main Air Consumption: 15 scim.
Calibration Point: 9 psig branch line pressure when ambient equals setpoint (factory-set).
Setpoint Adjustment: Serrated thumbwheel.
SKU:
BARBER COLMAN:2212-118
This product must be purchased in increments of 1
The Barber Colman (Schneider Electric) 2212-118 Direct Acting, Two-Pipe Thermostat, 55 to 85F, w/o Dial Limit Stops, Kit includes hardware/fittings, metal base, tube, cover, and instructions (2212-118-1).
The 2212-118 and 2212-119 Series Pneumatic Room Thermostats are designed for proportional control of pneumatic devices and actuators in environmental control systems. These two-pipe thermostats incorporate a highly sensitive bimetal thermostatic element and a pilot operated relay with pneumatic feedback for accuracy and stability over the entire operating range.
These thermostats have a serrated thumb wheel for setpoint adjustment
Specifications
Action: Proportional.
Setpoint Range: 55 to 85 °F (13 to 29 °C).
Throttling Range: 2 to 12 °F, adjustable.
Supply Air Pressure: 20 psig.
Maximum Air Pressure: 30 psig.
Main Air Consumption: 15 scim.
Calibration Point: 9 psig branch line pressure when ambient equals setpoint (factory-set).
Setpoint Adjustment: Serrated thumbwheel.